Study Energy Consumption and Loads with the Fluke 1735

Fluke_1735For electricians or technicians who need basic power quality logging, the Fluke 1735 Three-Phase Power Logger is set it up in seconds, and is capable of monitoring and recording most power parameters for up to 45 days.

 

 

Fluke 1735 Three-Phase Power Logger Specifications

General

Display

¼ VGA Graphic Color transmissive displays 320 x 240 Pixel with additional background lighting and adjustable contrast, text and graphics in color

Quality

Developed, designed and manufactured according to DIN ISO 9001

Memory

4 MB Flash memory, 3.5 MB for measuring data

Interface

RS-232 SUB-D socket; 115.2 k Baud, 8 data bits, no parity, 1 stop bit, firmware updates are possible with the RS- 232 interface (9-pole extension cable)

Sample rate

10.24 kHz

Line frequency

50 Hz or 60 Hz, user-selectable, with automatic synchronization

Power supply

NiMH battery-pack, with ac adapter (15 V to 20 V / 0.8 A)

Operation time with battery

Typical > 12 hours without backlight and > 6 hours with backlight high

Dimensions

240 x 180 x 110 mm

Weight

1.7 kg, including battery

Ambient conditions

Working temperature range

-10°C to +50°C

Storage temperature range

-20°C to +60°C

Operating temperature range

0°C to +40°C

Reference temperature range

23°C ±2°C

The above terms are defined in European Standards. To calculate the specification at any point in the working temperature range, use the temperature coefficient below.

Temperature coefficient

±0.1% of the measured value per°C from the reference

Intrinsic error

Refers to reference temperature, maximum deviation is guaranteed for two years

Operating error

Refers to operating temperature range, maximum deviation is guaranteed for two years

Climatic class

C1 (IEC 654-1) -5°C to +45°C, 5% to 95% RH, no dew

Housing

Cycoloy shock and scratch proof thermoplast V0-type (non-flammable) with rubber protection holster

EMC

Emission

IEC/EN 61326-1:1997 class B

Immunity

IEC/EN 61326-1:1997

Safety

Safety

IEC 61010-1 600 V CAT III, double or reinforced insulation, pollution degree 2

Protection

IP65; EN60529 (refers only to the main housing without the battery compartment)

RMS values are measured with a 20 ms resolution.

V-rms wye measurement

Measuring range

57 V/66 V/110 V/120 V/127 V/220 V/230 V/240 V/260 V/277 V/347 V/380 V/400 V/417 V/480 V AC

Intrinsic error

±(0.2% of measured value + 5 digits)

Operating error

±(0.5% of m. v. + 10 digit)

Resolution

0.1 V

V-rms delta measurement

Measuring range

100 V/115 V/190 V/208 V/220 V/380 V/400 V/415 V/450 V/480 V/600 V/660 V/690 V/720 V/830 V AC

Intrinsic error

±(0.2% of m. v. + 5 digit)

Operating error

±(0.5% of m. v. + 10 digit)

Resolution

0.1 V

A-rms measurement

Flexi set I ranges

15 A/150 A/3000 A rms (at sine)

Current clamp ranges

1 A/10 A

Resolution

0.01 A

Ranges

150 A/3000 A and 1 A/10 A

Intrinsic error

±(0.5% of m. v. + 10 digit)

Operating error

±(1% of m. v. + 10 digit)

Ranges

15 A

Intrinsic error

±(0.5% of m. v. + 20 digit)

Operating error

±(1% of m. v. + 20 digit)

 

The errors of the current probes are not considered.

By using Flexi-set

Flexi Set measuring error

±(2% of m. v. + 10 digit)

Position influence

±(3% of m. v. + 10 digit)

CF (typical)

2.83

When using Flexi Set please make sure to position the conductor opposite to the Flexi Set-lock

Power measurement (P – Active, S – Apparent, Q- Reactive, D – Distorting

Measuring range

see V rms and A rms measurement

Power errors are calculated by adding the errors of voltage and current

Additional error due to power factor PF

Specified error x (1-[PF])

Maximum range with voltage range 830 V delta-connection and 3000 A current range is 2.490 MW, higher displayed values possible when using PTs and CTs with ratio feature

Intrinsic error

±(0.7% of m.v. +15 digit)

Resolution

1 kW

Operating error

±(1.5% of m.v. + 20 digit)

Typical range with voltage range 230 V wye connection and 150 A current range is 34.50 KW.

Intrinsic error

±(0.7% of m.v. +15 digit)

Resolution

1 W to 10 W

Operating error

±(1.5% of m.v. + 20 digit)

The errors of the current sensors themselves have not been considered.

Energy measurement (kWh, KVAh, kVARh)

Intrinsic error

±(0.7% of m.v.+ F variation error* + 15 digit)

Resolution

1 W to 10 W

Operating error

±(1.5% of m.v. + F variation error1 + 20 digit)

 

1. Frequency variation error

PF (Power factor)

Range

0.000 to 1.000

Resolution

0.001

Accuracy

±1% of full scale

Frequency measurement

Measuring range

46 Hz to 54 Hz and 56 Hz to 64 Hz

Intrinsic error

±(0.2% of m. v. + 5 digit)

Operating error

±(0.5% of m. v.+ 10 digit)

Resolution

0.01 Hz

Harmonics

Measuring range

To 50th harmonic (< 50% of nom)

Accuracy

Vm, Im, THDV, THDI

IEC 61000-4-7:2002, Class II

Vm ≥ 3% Vn

±5% Vm

Vm < 3% Vnom

±0.15% Vnom

Im ≥ 10% Inom

±5% Im

Im < 10% Inom

±0 5% Inom

THDV

for THD < 3% ±0.15% at Vnom

for THD ≥ 3% ±5% at Vnom

THDI

for THD < 10% ±0.5% at Inom

for THD ≥ 10% ±5% at Inom

Vnom

Normal voltage range

Inom

Nominal current range

Vm and Im are measured values of harmonic m

Events

 

Detection of voltage dips, voltage swells and voltage interruptions with a 10 ms resolution and measuring error of the half period sine wave of rms.

Intrinsic error

±(1% of m.v. + 10 digit)

Operating error

±(2% of m.v. + 10 digit)

Resolution

0.1 V