Skip to content

Specifications for the Doble TDR9000 Circuit Breaker Test System

  • Uncategorized
Doble_TDR9100The Doble TDR9000 Circuit Breaker Test System high-speed data acquisition circuitry, coupled with interference suppression designed for substation environments, provides accurate test results and records contact bounce time as low as 60 μs. Its modular design allows you to acquire a circuit breaker test system matched to your present needs and upgrade as required.

 

 

 

Doble TDR9000 specifications:

Motion Channels

Number of Channels:

3 – up to 9 with ganged units

Connector:

15-pin “D”

Voltage Isolation to Chassis:

1.0 kV

 

Event Channels

Dual function, Analog or Auxiliary, user programmable

Number of Channels:

6 – up to 18 with ganged units

 

 Analog Measurement Channels

Maximum Input Voltage:

± 300 V

 Input Impedance:

1 MΩ

 Resolution:

12 Bit

 Number of Ranges:

 Ten 0.2 to 300 V

 Analog Accuracy:

± 1% of reading, ± 1.5% full scale offset

 Voltage Isolation to Chassis:

1.0 kV

 

Auxiliary Contact Channels

 Sense Mode:

Voltage Sense/Contact Sense

 Maximum Input Voltage:

± 300 V

 Open Circuit Voltage:

30 V ± 10%

 Close Circuit Current:

28 mA ± 10%

 Voltage Isolation to Chassis:

1.0 kV

 

Digital Linear/Rotary Motion Transducer

 

 

Linear

Rotary

Range:

0.0 to 40.0”
0.0 to 1000.0 mm

0.0 to 2880.0°

Accuracy:

+/0.1% of the value

+/0.1” max error

+/0.1% of the value
+/0.1° max error

Measurement

 

 

Resolution:

0.00125”
0.03 mm

0.09°

Velocity:

50 ft/s
15 m/s

120 rev/s max

Acceleration:

1200 g for 50 µs max

30×106°/s2 max

 

General

Recordings:

25 seconds (all channels at max resolution)
Up to 87 minutes (reduced resolution)

Communication:

USB or Ethernet

Safety:

Safety Ground
Remote Safety Switch
Audible Indication (test in progress)

Pending Certifications:

CE, C Tick, CSA Compliant

Available for rent, lease, or purchase from Protec Equipment Resources.  We are here to help you with your testing equipment needs.