The maintenance of an adequate low resistance ground connection is essential to both the protection and performance of any electrical system. Ground testing should be performed both upon installation, to meet design specification, and periodically thereafter in order to maintain service.
The Megger DET4TCR2 Ground Resistance Test Kit can perform bonding tests (using an ac signal), to determine that adequate connection has been made from equipment to the grounding system, and can perform soil resistivity tests.
Megger DET4TCR2 Ground Resistance Test Kit Specifications
Resistance range: 0.01 to 200 kΩ autoranging
Resistance accuracy:
2P measurements 2% ±3 digits
3P measurements 2% ±3 digits
4P measurements 2% ±3 digits
ART measurements 5% ±3 digits
Stakeless measurements 7% ±3 digits
Maximum probe resistance:
Rp limit: 200kΩ (50V output voltage)
Rc limit: 200kΩ (50V output voltage)
Limits reduced to 100kΩ for 25V output voltage
Limits reduced to 5kΩ for 0.01 Ω resolution
Earth voltage range: 0 – 100 V
Earth voltage accuracy: 2% ±2 V
2-wire test: Yes
3-wire test: Yes
4-wire test: Yes
Stakeless test: Yes
Ground current range (with current measuring clamp): 0.5 mA to 19.9 A
Ground current accuracy: 5% ±3 digits
Display: 3-1/2 digit high contrast LCD, backlit
Test frequency: 94, 105, 111 and 128 Hz
Test voltage: 25 V or 50 V, user selectable (factory setting 50 V)
Test current: 450 micro-amps at 25 V or 50 V (selectable), 4.5 mA at 25 V
Noise rejection: 40V pk to pk
Noise check: Automatic
C spike check: Automatic
P spike check: Automatic
Battery type: 8 1.5 V AA NiMH rechargeable cells
Battery life: 3 hours, 700 consecutive tests
Safety: EN61010-1 CAT IV 100 V
Terminals: 4 mm plug type (test leads)
Ingress protection: IP54
EMC: Meets the requirements of EN61326-1:1998 for use in heavy industrial areas, including amendment 1
Dimensions: 8 x 5.7 x 3.2 in. (203 x 148 x 78 mm)
Weight: 2.2 lb (1 kg)
Operating temperature range: 5º to +131º F (-15º to +55º C)
Storage temperature range: -40º to +158º F (-40º to +70º C)
Humidity: 95% RH non-condensing at 104º F (40º C)