The Megger BITE 2P Battery Impedance Test Set determines the condition of lead-acid and nickel-cadmium cells up to 7000 Ah.
An advanced feature set has been developed that includes Pass/Warning/Fail calculations based on a user-entered baseline value, advanced printing functions and more.
The case of the Megger BITE 2P consists of both the transmitter and a carrying case for all of the standard accessories and some of the optional accessories, in an all-in-one unit.
The instrument works by applying a test signal across the battery string while on-line, then calculates impedance based on simultaneous measurements of current and resulting voltage drop of each cell/jar.
The Megger BITE 2P also measure dc voltage and interconnection (strap) resistance to help determine the overall condition of the entire battery string’s electrical path from terminal plate to terminal plate.
Megger BITE 2P Specifications:
Application
Test lead-acid and nickel-cadmium cells up to 7000 Ah.
Maximum Total Voltage at Current Source Leads
275 V dc (larger battery systems can be sectioned to accommodate this specification)
Transmitter
Supply Voltage
100 to 130 V, 50/60 Hz, 200 VA max
210 to 250 V, 50/60 Hz, 200 VA max
Source Output Current
10 A nominal, 50/60 Hz operation
Maximum Battery String Test Voltage
275 V dc at source lead terminals (section the battery if >275 Vdc)
Display
Digital LCD meter, 0 to 15 A
Printer
Built-in thermal, with 4.25 in. (110 mm) printing width
Charger
Supply Voltage
100 to 130 V, 50/60 Hz, 14 VA
210 to 250 V, 50/60 Hz, 14 VA
Output
6.50 V dc @ 1.10 A dc charging (max)
9.60 V dc open circuit
Receiver
Accuracy
ac impedance 5% +1 LSD
dc voltage ±(0.5% of rdg +1 LSD)
Precision
Better than 0.5% one sigma
Voltage Range and Resolution
1 to 2.500 V dc, 1 mV resolution
2.5 to 25.00 V dc, 10 mV resolution
Impedance Range and Resolution
0 to 1.000 mΩ, 1µΩ resolution
1 to 10.00 mΩ, 10µΩ resolution
10 to 100.0 mΩ, 0.1mΩ resolution
Setting Time per Reading
3 seconds maximum
Display
LCD, 2 x 16 characters
Supply
4.8 V dc, 800 mAh, quick charge nickel-cadmium battery pack
Battery Pack Life, Full Charge
5 hours continuous
Maximum Cell/Jar Test Voltage
25 V dc between receiver and potential probe
Temperature
Operating: 32 to 105° F (0 to 40° C)
Storage: -5 to 130° F (-20 to 55° C)
Humidity: 20 to 90% RH, noncondensing
Clamp Range
Standard CT
2.0 in. (50 mm) maximum opening
Optional Miniature CT
0.5 in. (12 mm) maximum opening
Optional RopeCTTM
12 in. (300 mm) opening, approx.
Safety
Designed to meet IEC 61010-1
Dimensions
Transmitter
7.5 H x 18.5 W x 14.6 D in. (19 H x 47 W x 37 D cm)
Receiver (irregular shape)
7.25 H x 11.25 W x 2 D in. (18 H x 29 W x 5 D cm)
Weight
Transmitter
18 lb (8.2 kg) alone, 32 lb (14.5 kg) packed
Receiver
1.6 lb (0.7 kg