Skip to content

ETI PI-6000 Output Current and Overload Capabilities

  • Uncategorized
ETI_PI6000

An advanced primary injection test set, the ETI PI-6000 is capable of testing circuit breakers up to 6000 amperes frame size. It incorporates an output transformer with dual primaries to facilitate its use on power sources of 480 VAC as well as 240 and 208 VAC.

Using SCR’s the ETI PI-6000 Primary Circuit Breaker Test Set eliminates closing time errors. Initiation at the zero crossover point eliminates DC offset in the current waveform and results in accurate, repeatable test results even with short-duration currents for high speed solid state or electromechanical trip devices.

ETI PI-6000 Primary Circuit Breaker Test Set Output Current & Overload Capabilities

9V

(Parallel)

 

18 V

(Series)

 

Overload

 

Duty

Max ON

Time

 

Min OFF

Time

Max Input

Current

480 V

6000 A

3000 A

1X

100%

Continuous

N/A

121 Amps

8400 A

4200 A

1.4 X

50%

15 Min

15 Min

175 Amps

12000 A

6000 A

2 X

25%

5 Min

15 Min

260 Amps

18000 A

9000 A

3 X

10%

1.5 Min

15 Min

415 Amps

24000 A

12000 A

4 X

6%

45 Sec

15 Min

582 Amps

30000 A

15000 A

5 X

4%

4 Sec

2 Min

776Amps

42000 A*

21000 A*

7 X

2%

2 Sec

2 Min

1208 Amps

60000 A*

30000 A*

10 X

1%

1 Sec

2 Min

1982 Amps

Each Protec office maintains a full complement of electrical test and measurement equipment. Offering equipment from all of the premiere manufacturers for rent, lease or purchase, Protec has the electrical testing equipment you need to get the job done.

 